TeSys GV motor circuit breaker, 3 poles (3P), 0.4A/690V, for 3-phase motor applications 0.09kW@400V. It provides a thermal-magnetic protection with a thermal setting range 0.25-0.4A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh). Specifications Main Range TeSys Deca Product name TeSys GV2 TeSys Deca Product or component type Motor circuit breaker Device short name GV2ME Device application Motor protection Trip unit technology Thermal-magnetic Complementary poles description 3P Network type AC Utilisation category Category A IEC 60947-2 AC-3 IEC 60947-4-1 AC-3e IEC 60947-4-1 Network frequency 50/60 Hz IEC 60947-4-1 Fixing mode 35 mm symmetrical DIN rail clipped Panel screwed with adaptor plate) Motor power kW 0.09 kW 400/415 V AC 50/60 Hz Breaking capacity 100 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 100 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 100 kA Icu 440 V AC 50/60 Hz IEC 60947-2 100 kA Icu 500 V AC 50/60 Hz IEC 60947-2 100 kA Icu 690 V AC 50/60 Hz IEC 60947-2 [Ics] rated service short-circuit breaking capacity 100 % 230/240 V AC 50/60 Hz IEC 60947-2 100 % 400/415 V AC 50/60 Hz IEC 60947-2 100 % 440 V AC 50/60 Hz IEC 60947-2 100 % 500 V AC 50/60 Hz IEC 60947-2 100 % 690 V AC 50/60 Hz IEC 60947-2 Control type Push-button [In] rated current 0.4 A Thermal protection adjustment range 0.25…0.4 A IEC 60947-4-1 Magnetic tripping current 5 A [Ith] conventional free air thermal current 0.4 A IEC 60947-4-1 [Ue] rated operational voltage 690 V AC 50/60 Hz IEC 60947-2 [Ui] rated insulation voltage 690 V AC 50/60 Hz IEC 60947-2 [Uimp] rated impulse withstand voltage 6 kV IEC 60947-2 Phase failure sensitivity Yes IEC 60947-4-1 Suitability for isolation Yes IEC 60947-1 § 7-1-6 Power dissipation per pole 2.5 W Mechanical durability 100000 cycles Electrical durability 100000 cycles AC-3 415 V In 100000 cycles AC-3e 415 V In Rated duty Continuous IEC 60947-4-1 Tightening torque 15.05 lbf.in (1.7 N.m) screw clamp terminal Width 1.8 in (45 mm) Height 3.5 in (89 mm) Depth 3.09 in (78.5 mm) Net weight 0.57 lb(US) (0.26 kg) Colour Dark grey