This product is part of the Modicon M221 range, an offer of programmable logic controllers for hardwired architectures. This logic controller provides 9 discrete inputs and 7 relay ethernet outputs with 10bit input resolution, normally opened relay output. It is a Modicon logic controller with a rated supply voltage of 100V to 240V AC, an output voltage of 5V to 125V DC, 5V to 250V AC and an output current of 2A with sink or source input logic. This product requires minimal installation and offers tremendous versatility. Integrated connections are USB port with mini B USB 2.0 connector, non isolated serial link serial 1 with RJ45 connector and RS232/RS485 interface and ethernet with RJ45 connector. It is a Modicon M221 controller with a network frequency of 50/60Hz, 256KB for internal variables RAM, user application and data RAM, a built-in flash memory of 256KB and a SD card memory capacity of 2GB. It is an IP20 rated product. Its dimensions are 95mm (Width) x 70mm (Depth) x 90mm (Height). It weighs 0.346kg. This product is certified by CE, IACS E10, RCM, ABS, LR, DNV-GL, CSA, EAC and CULus. It meets EN/IEC 60664-1, EN/IEC 61131-2 and EN/IEC 61010-2-201 standards. It supports DIN rail mount. Achieve benchmark performance while increasing profitability with the Modicon M221 through intuitive machine programming with SoMachine Basic, ready-to-use applications and function blocks.
Specifications
Main
range of product Modicon M221
Product or component type Logic controller
[Us] rated supply voltage 100...240 V AC
Discrete input number
9, discrete input IEC 61131-2 Type 1
Analogue input number 2 0...10 V
discrete output type Relay normally open
Discrete output number 7 relay
Discrete output voltage
5...125 V DC
5...250 V AC
Discrete output current 2 A
Complementary
Discrete I/O number 16
Maximum number of I/O expansion module
4 local
11 remote
Supply voltage limits 85…264 V
Network frequency 50/60 Hz
Inrush current 40 A
Maximum power consumption in VA
49 VA 100...240 V with max number of I/O expansion module
33 VA 100...240 V without I/O expansion module
Power supply output current
0.325 A 5 V expansion bus
0.12 A 24 V expansion bus
Discrete input logic Sink or source (positive/negative)
Discrete input voltage 24 V
discrete input voltage type DC
analogue input resolution 10 bits
LSB value 10 mV
Conversion time
1 ms per channel + 1 controller cycle time analog input
Permitted overload on inputs
+/- 30 V DC 5 min maximum)analog input
+/- 13 V DC permanent)analog input
Voltage state 1 guaranteed >= 15 V input
Voltage state 0 guaranteed <= 5 V input
Discrete input current
7 mA discrete input
5 mA fast input
Input impedance
3.4 kOhm discrete input
100 kOhm analog input
4.9 kOhm fast input
Response time
35 µs turn-off, I2...I5 input
10 ms turn-on output
10 ms turn-off output
5 µs turn-on, I0, I1, I6, I7 fast input
35 µs turn-on, other terminals input
5 µs turn-off, I0, I1, I6, I7 fast input
100 µs turn-off, other terminals input
Configurable filtering time
0 ms input
3 ms input
12 ms input
Output voltage limits
125 V DC
277 V AC
Maximum current per output common
6 A COM 1
7 A COM 0
Absolute accuracy error
+/- 1 % of full scale analog input
Electrical durability
100000 cycles AC-12, 120 V, 240 VA, resistive
100000 cycles AC-12, 240 V, 480 VA, resistive
300000 cycles AC-12, 120 V, 80 VA, resistive
300000 cycles AC-12, 240 V, 160 VA, resistive
100000 cycles AC-15, cos phi = 0.35, 120 V, 60 VA, inductive
100000 cycles AC-15, cos phi = 0.35, 240 V, 120 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 120 V, 18 VA, inductive
300000 cycles AC-15, cos phi = 0.35, 240 V, 36 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 120 V, 120 VA, inductive
100000 cycles AC-14, cos phi = 0.7, 240 V, 240 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 120 V, 36 VA, inductive
300000 cycles AC-14, cos phi = 0.7, 240 V, 72 VA, inductive
100000 cycles DC-12, 24 V, 48 W, resistive
300000 cycles DC-12, 24 V, 16 W, resistive
100000 cycles DC-13, 24 V, 24 W, inductive (L/R = 7 ms)
300000 cycles DC-13, 24 V, 7.2 W, inductive (L/R = 7 ms)
Switching frequency
20 switching operations/minute with maximum load
Mechanical durability 20000000 cycles relay output
Minimum load 1 mA 5 V DC relay output
Protection type Without protection 5 A
Reset time 1 s
Memory capacity
256 kB user application and data RAM 10000 instructions
256 kB internal variables RAM
Data backed up
256 kB built-in flash memory backup of application and data
Data storage equipment 2 GB SD card optional)
Battery type BR2032 or CR2032X lithium non-rechargeable
Backup time 1 year 77 °F (25 °C) by interruption of power supply)
Execution time for 1 KInstruction 0.3 ms event and periodic task
Execution time per instruction 0.2 µs Boolean
Exct time for event task 60 µs response time
Maximum size of object areas
255 %C counters
512 %KW constant words
255 %TM timers
512 %M memory bits
8000 %MW memory words
Realtime clock With
Clock drift <= 30 s/month 77 °F (25 °C)
Regulation loop
Adjustable PID regulator up to 14 simultaneous loops
Counting input number
4 fast input (HSC mode) 100 kHz 32 bits
counter function
Pulse/direction
A/B
Single phase
Integrated connection type
USB port mini B USB 2.0
Non isolated serial link serial 1 RJ45 RS232/RS485
Ethernet RJ45
Supply
Serial)serial link supply 5 V, <200 mA
Transmission rate
1.2...115.2 kbit/s (115.2 kbit/s by default) 49.21 ft (15 m) RS485
1.2...115.2 kbit/s (115.2 kbit/s by default) 9.84 ft (3 m) RS232
480 Mbit/s USB
Communication port protocol
USB port USB - SoMachine-Network
Non isolated serial link Modbus master/slave - RTU/ASCII or SoMachine-Network
Ethernet
Port Ethernet
10BASE-T/100BASE-TX 1 328.08 ft (100 m) copper cable
Communication service
DHCP client
Ethernet/IP adapter
Modbus TCP server
Modbus TCP slave device
Modbus TCP client
Local signalling
PWR 1 LED green)
RUN 1 LED green)
Module error (ERR) 1 LED red)
SD card access (SD) 1 LED green)
BAT 1 LED red)
I/O state 1 LED per channel green)
SL 1 LED green)
ACT Ethernet network activity green)
Link (Link Status) Ethernet network link yellow)
Electrical connection
Removable screw terminal block for inputs
removable screw terminal block for outputs
terminal block, 3 for connecting the 24 V DC power supply
connector, 4 for analogue inputs
Mini B USB 2.0 connector for a programming terminal
Maximum cable distance between devices
Shielded cable <32.81 ft (10 m) fast input
Unshielded cable <98.43 ft (30 m) output
Unshielded cable <98.43 ft (30 m) digital input
Unshielded cable <3.28 ft (1 m) analog input
Insulation
Between input and internal logic 500 V AC
Non-insulated between analogue input and internal logic
Non-insulated between analogue inputs
Between supply and ground 1500 V AC
Between sensor power supply and ground 500 V AC
Between input and ground 500 V AC
Between output and ground 1500 V AC
Between supply and internal logic 2300 V AC
Between sensor power supply and internal logic 500 V AC
Between output and internal logic 2300 V AC
Between Ethernet terminal and internal logic 500 V AC
Between supply and sensor power supply 2300 V AC
Marking CE
Sensor power supply
24 V DC 250 mA supplied by the controller
Mounting support
Top hat type TH35-15 rail IEC 60715
Top hat type TH35-7.5 rail IEC 60715
plate or panel with fixing kit
height 3.54 in (90 mm)
Depth 2.76 in (70 mm)
Width 3.74 in (95 mm)
Net weight 0.76 lb(US) (0.346 kg)