Specifications Main Product Single throw safety switch Duty Rating Reinforced device function Heavy application Disconnect Type Fuse disconnect Neutral factory installed Field installed kit available Number of poles 3 Rated current 60 A Voltage Rating 600 V AC/DC Enclosure Rating NEMA 4X stainless steel 304 breaking capacity 15 hp at 480 V AC 50...60 Hz for 3 phases motors 30 hp at 480 V AC 50...60 Hz for 3 phases motors 15 hp at 600 V AC 50...60 Hz for 3 phases motors 50 hp at 600 V AC 50...60 Hz for 3 phases motors 30 hp at 600 V DC Complementary Short circuit current 10 kA for H, K, J or R without fuse rejection clips 200 kA for R with fuse rejection clips 200 kA for J fuse type H or K R or J Mounting type Surface-mounted Electrical connection Lugs wiring configuration Type 3 wires with neutral Wire size AWG 14...AWG 3 copper AWG 12...AWG 3 aluminum tightening torque 5.65 N.m (AWG 3) 5.08 N.m (AWG 6...AWG 4) 4.52 N.m for 8.367 mm² (AWG 8) 5.65 N.m for 2.06…5.261 mm² (AWG 14...AWG 10) depth 184.40 mm width 226.57 mm height 430.02 mm weight 10 kg Grounding kit Original installation (factory) Service entrance Service entrance suitable for the United States Service entrance suitable for Mexico Environment Certifications UL E2875 Listed File