Specifications Main Product Single Throw Safety Switch Duty Rating Heavy duty Device application Heavy application Disconnect Type Non-fusible disconnect Factory Installed Neutral Field installed kit available Number of Poles 3 Current Rating 200 A Voltage Rating 600 V AC/DC Enclosure Rating NEMA 12 galvannealed steel Motor power hp 15 hp at 240 V AC 50/60 Hz for 1 phase motors 60 hp at 240 V AC 50/60 Hz for 3 phases motors 50 hp at 480 V AC 50/60 Hz for 1 phase motors 125 hp at 480 V AC 50/60 Hz for 3 phases motors 50 hp at 600 V AC 50/60 Hz for 1 phase motors 150 hp at 600 V AC 50/60 Hz for 3 phases motors 40 hp at 250 V DC 50 hp at 600 V DC Complementary Mounting Type Surface Electrical Connection Lugs Wiring configuration 3-wire Wire Size AWG 6...250 kcmil copper or aluminum Tightening torque 275 lbf.in (31.07 N.m) 0.02…0.20 in² (13.3…127 mm²) AWG 6...250 kcmil) Depth 9.02 in (229.11 mm) Width 17.01 in (432.05 mm) height 28.93 in (734.82 mm) Net weight 52.01 lb(US) (23.59 kg) Grounding Kit Factory installation Service Entrance Suitable service entrance for USA Suitable service entrance for Mexico Environment Certifications UL listed file E2875