Enhance the performance and longevity of your electrical systems with the Marcus MLR0002M12 Line Reactor. Designed to mitigate common line problems such as harmonic distortion, nuisance tripping, line notching, and line noise, this reactor also protects against surge currents. By limiting inrush current to rectifiers and reducing peak current, it effectively minimizes current and voltage distortion, leading to improved waveform quality. This results in extended life for switching components in power electronic circuits and motors, reduced operating temperatures, and decreased motor noise. Built with advanced grade laminations, it ensures no saturation even under extreme overload conditions. Its compact design, due to heat-proof insulation, and low heat dissipation contribute to efficient operation and minimal power losses.The Marcus MLR0002M12 is an open-style, three-phase line reactor with a voltage rating of 480V and an amperage rating of 2A. It features an inductance of 12 mH, an impedance of 3%, and a power rating of 1 hp. The reactor is designed for a 60 Hz frequency and has a temperature rating of 155 deg C. Its dimensions are 4.40 inches in length, 3.25 inches in height, and 2.85 inches in width, with mounting holes measuring 0.28 x 0.56 inches. The product has losses of 6 watts.